Estimativa de massa de fluido refrigerante em um evaporador utilizando diferentes correlações de fração de vazio com a linguagem modelica
Show simple item record
dc.contributor |
Universidade Federal de Santa Catarina |
pt_BR |
dc.contributor.advisor |
Lôndero da Silva, Diogo |
|
dc.contributor.author |
Goulart Duarte, Lucas |
|
dc.date.accessioned |
2021-05-18T15:32:26Z |
|
dc.date.available |
2021-05-18T15:32:26Z |
|
dc.date.issued |
2021-05-06 |
|
dc.identifier.uri |
https://repositorio.ufsc.br/handle/123456789/223211 |
|
dc.description |
TCC (graduação) - Universidade Federal de Santa Catarina. Campus Joinville. Engenharia Naval. |
pt_BR |
dc.description.abstract |
Este trabalho apresenta a estimativa de massa de fluido refrigerante em um evaporador,
utilizando diferentes correlações de fração de vazio implementadas em software
comercial baseado na linguagem Modelica. O objetivo do estudo foi estimar a massa
de fluido refrigerante presente no evaporador de um sistema de refrigeração, utilizando
diferentes correlações de fração de vazio. O evaporador é semelhante às unidades
utilizadas na refrigeração de contêineres marítimos. As correlações selecionadas
apresentam o R-290 em seus bancos de dados. O R-290 é um fluido refrigerante
natural com forte apelo ambiental devido ao seu baixíssimo GWP (Potencial de
Aquecimento Global) de valor 3 e ODP (Potencial de Destruição do Ozônio) nulo.
Nesse trabalho, a comparação entre resultados experimentais e de simulações foi
possível pelo trabalho em conjunto com o Instituto de pesquisa Fraunhofer ISE, que
realizou um teste de bancada utilizando a técnica QCV (Quick Closing Valve). Os
resultados obtidos apontaram a correlação de Kanizawa e Ribatski (2016) como a mais
precisa, com diferença de 4,0% entre valores simulados e experimentais da quantidade
de massa de fluido refrigerante no interior do evaporador. Em seguida, a correlação de
Bhagwat e Ghajar (2014) apresenta diferença de 8,8% entre resultados simulados e
experimentais da quantidade de massa de fluido refrigerante. |
pt_BR |
dc.description.abstract |
This work presents the estimation of refrigerant charge in an evaporator, using different
void fraction correlations implemented in a commercial software based on the Modelica
language. The objective of the study was to estimate the refrigerant charge using
diverse void fraction. The evaporator is similar to maritime transport’s unities. The
selected correlations have the refrigerant R-290 Propane in their database. R-290 is a
natural refrigerant with strong environmental appeal due to its very low GWP (Global
Warming Potential) value of 3 and zero ODP (Ozone Depleting Potential). In this work,
the comparison between experimental and simulation results was made possible by
working together with the Fraunhofer Research Institute ISE, which conducted a bench
test using the QCV (Quick Closing Valve) technique. The results obtained pointed to
the correlation by Kanizawa and Ribatski (2016) as the most accurate, with difference
of 4.0% between numerical and experimental results regarding the refrigerant charge
within the evaporator. Followed by the correlation by Bhagwat and Ghajar (2014) with
difference of 8.0% between the numerical and experimental refrigerant charge in the
evaporator. |
pt_BR |
dc.format.extent |
73 f. |
pt_BR |
dc.language.iso |
pt_BR |
pt_BR |
dc.publisher |
Joinville, SC |
pt_BR |
dc.rights |
Open Access |
|
dc.subject |
Evaporador |
pt_BR |
dc.subject |
Fração de vazio |
pt_BR |
dc.subject |
Massa de fluido refrigerante |
pt_BR |
dc.subject |
Modelica |
pt_BR |
dc.subject |
QCV |
pt_BR |
dc.title |
Estimativa de massa de fluido refrigerante em um evaporador utilizando diferentes correlações de fração de vazio com a linguagem modelica |
pt_BR |
dc.type |
TCCgrad |
pt_BR |
dc.contributor.advisor-co |
Will, Torsten |
|
Files in this item
This item appears in the following Collection(s)
Show simple item record
Search DSpace
Browse
-
All of DSpace
-
This Collection
My Account
Statistics
Compartilhar