dc.description.abstract |
No contexto marítimo, a refrigeração surge da necessidade de transportar cargas
perecíveis, mantendo suas características de qualidade por mais tempo durante as
longas viagens. Inicialmente, o alto custo financeiro da refrigeração tornou a sua
utilização inviável, mas, com os avanços tecnológicos e a crescente demanda das
viagens marítimas europeia, durante século XIX, permitiu contornar esse problema.
Nesse caso, a evolução desses sistemas e a especialização das embarcações
levaram à consolidação do transporte por contêineres refrigerados, especialmente em
navios de múltiplos propósitos. Entretanto, os sistemas de refrigeração são
suscetíveis a falhas, tais como a parada de algum componente ou vazamento da carga
de fluido refrigerante. Para evitar esse tipo de situação, é necessária a utilização de
sistemas altamente confiáveis que minimizem a possibilidade de danos à carga e
prejuízos financeiros. Diante desse contexto, o objetivo do presente trabalho é propor
um método preditivo para a identificação de falhas em sistemas de refrigeração
utilizados em contêineres refrigerados, com ênfase na detecção de vazamentos de
fluidos refrigerantes. Para tanto, no laboratório de refrigeração Veicular, ReVe,
localizado no campus Joinville da Universidade Federal de Santa Catarina, foi
implementado um modelo computacional para a detecção de vazamento de fluido
refrigerante. O aparato experimental utilizado consiste em um sistema de produção
de frio instrumentado. Os dados experimentais foram empregados para validação do
modelo, que permitiu prever a carga de fluido refrigerante com erros máximos de ±7%
em relação a carga real. Um método capaz de prever vazamentos de fluido
refrigerante em contêineres refrigerados antes que eles comprometam a capacidade
de refrigeração oferece vantagens significativas para a operação e conservação de
cargas sensíveis à temperatura. A principal vantagem é a possibilidade de realizar
manutenções preventivas de forma mais eficiente, evitando falhas no sistema que
poderiam resultar na perda total da carga transportada. O método também aumenta a
vida útil dos equipamentos, minimiza custos operacionais com reparos. |
pt_BR |
dc.description.abstract |
In the maritime context, refrigeration arises from the need to transport perishable
cargo, maintaining its quality characteristics for longer during long voyages. Initially,
the high financial cost of refrigeration made its use unfeasible, but technological
advances and the growing demand for European sea travel during the 19th century
made it possible to overcome this problem. In this case, the evolution of these systems
and the specialization of vessels led to the consolidation of transport by refrigerated
containers, especially in multi-purpose vessels. However, refrigeration systems are
susceptible to failures, such as the failure of a component or leakage of the refrigerant
load. To avoid this type of situation, it is necessary to use highly reliable systems that
minimize the possibility of damage to the cargo and financial losses. Given this context,
the objective of this work is to propose a predictive method for identifying failures in
refrigeration systems used in refrigerated containers, with an emphasis on detecting
refrigerant leaks. To this end, a computational model for detecting refrigerant leaks
was implemented at the ReVe Vehicle Refrigeration Laboratory, located at the Joinville
campus of the Federal University of Santa Catarina. The experimental apparatus used
consists of an instrumented cold production system. The experimental data were used
to validate the model, which allowed the refrigerant load to be predicted with maximum
errors of ±7% in relation to the actual load. A method capable of predicting refrigerant
leaks in refrigerated containers before they compromise the refrigeration capacity
offers significant advantages for the operation and conservation of temperature-
sensitive cargo. The main advantage is the possibility of performing preventive
maintenance more efficiently, avoiding system failures that could result in the total loss
of the transported cargo. The method also increases the useful life of the equipment
and minimizes operational costs with repairs. |
pt_BR |
dc.format.extent |
71 f. |
pt_BR |
dc.language.iso |
por |
pt_BR |
dc.publisher |
Joinville, SC. |
pt_BR |
dc.rights |
Open Access. |
en |
dc.subject |
Contêiner refrigerado |
pt_BR |
dc.subject |
Manutenção preditiva |
pt_BR |
dc.subject |
Carga de fluido refrigerante |
pt_BR |
dc.subject |
Tomada de decisão |
pt_BR |
dc.title |
Detecção preditiva de falhas em sistemas de refrigeração de contêineres com ênfase em vazamentos de carga de fluido refrigerante |