dc.description |
TCC(graduação) - Universidade Federal de Santa Catarina. Centro Tecnológico. Engenharia Sanitária e Ambiental. |
pt_BR |
dc.description.abstract |
O presente estudo de caso buscou analisar o potencial envolvido no uso de esgoto
tratado nas estações de Florianópolis/SC para combate a incêndio. O estudo
abrangeu a definição da demanda de água dos quarteis, a verificação do atendimento
a legislações da qualidade do efluente tratado, a probabilidade do contado direto desta
água com vítimas nos incêndios e duas propostas de implementação do sistema,
incluindo suas dificuldades e benefícios. A coleta de dados do Corpo de Bombeiros
Militar de Santa Catarina foi feita através da análise de registros no sistema interno do
CBMSC de 2018 a 2021 e entrevistas, estas do tipo informal realizadas com 15
bombeiros militares de plantão nos quarteis do município. Os dados das vazões das
estações em 2021 e dos parâmetros de saída do tratamento das estações de 2020 e
2021 foram fornecidos pela Companhia Catarinense de Água e Saneamento, e
comparados com a resolução conjunta SES/SIMA n°01 do estado de São Paulo que
define a qualidade do efluente tratado para fins urbanos. A demanda de água
encontrada para os seis quarteis militares de Florianópolis varia de 5.583 a 16.121 L
por semana, correspondendo a menos de 1% da menor vazão gerada pelas estações.
O atendimento a SES/SIMA n°01 analisou 7 dos 14 parâmetros solicitados, das seis
estações. A estação da Lagoa da Conceição obteve o maior número de parâmetros
dentro do solicitado (quatro), as demais estações obtiveram de três a uma análise
positivas. De todas as ocorrências de incêndio registradas nos últimos quatro anos,
apenas 3% tiveram vítimas atendidas, já as ocorrências que ocorrem em locais com
alta taxa de circulação de pessoas representam 38% dos registros. As propostas de
implementação do sistema incluem o abastecimento de cada quartel na estação de
esgoto mais próxima ou o fornecimento do efluente pela estação da Lagoa da
Conceição, a qual necessita de atualização de menos parâmetros de saída. Com esta
pesquisa infere-se que a implantação de um sistema de reuso de efluente tratado para
combate a incêndio em Florianópolis necessita da atualização e refinamento do
tratamento para atendimento a legislação, mas atende a demanda de água dos
quarteis e apresenta baixa probabilidade de contato de vítimas com o efluente. |
pt_BR |
dc.description.abstract |
This case study’s focus was to analyse the potential in the use of treated sewage water
in the firefighting stations in Florianópolis. The study covered the definition of the water
demands in the headquarters, verifying the compliance with local laws and regulations
regarding the treated effluent's quality, the probability of the victim's direct contact with
this water, two proposals for the implementation of the system and its difficulties and
benefits. Data collection from the Santa Catarina’s Military Fire Department was done
by analysing the records in the CBMSC’s internal system from to 2018 to 2021, and
also trough informal interviews with 15 military firefighters on duty in the city’s
headquarters. The information regarding the station’s outflows in 2021 and the
treatments output parameters of 2020 and 2021 were provided by Compania
Catarinense de Água e Saneamento, and compared with the resolution SES/SIMA
number 1 São Paulo’s state, that defines the effluent’s treatment for urban processes.
The amount of water demands in six military headquarters in Florianópolis varies from
5,583 to 16,121 litres per week, corresponding in less than 1 percent of the lowest flow
generated by the stations. SES/SIMA number 1 considered 7 of the 14 demanded
parameters, in all six stations. Lagoa da Conceição’s station registered the highest
number of parameters (four), the remaining stations registered from 1 to 3 positive
results. From all fire occurrences registered in the last four years, only 3% had attended
victims, whereas the ones that occur in places with high amount of people passing by
represents 38% of them. The system’s implementation proposal includes supplying
the headquarters with the water the nearest sewage station or with the effluent from
the Lagoa da Conceição’s station, which needs fewer outgoing parameters updates.
With this research its concluded that implementing an effluent reuse treated water
system for solving fire occurrences in Florianópolis needs improvement on the water
treatment to comply with the laws and regulations, but it meets the water demands in
the headquarters and it’s highly unlikely that the victims would have direct contact with
the water. |
pt_BR |
dc.format.extent |
76 f. |
pt_BR |
dc.language.iso |
por |
pt_BR |
dc.publisher |
Florianópolis, SC. |
pt_BR |
dc.rights |
Open Access |
|
dc.subject |
Florianópolis |
pt_BR |
dc.subject |
Reuso |
pt_BR |
dc.subject |
Combate a incêndio |
pt_BR |
dc.subject |
Esgoto |
pt_BR |
dc.subject |
Corpo de Bombeiros Militar |
pt_BR |
dc.title |
Potencialidades do aproveitamento de esgoto tratado em estações de tratamento para combate a incêndio em Florianópolis/SC |
pt_BR |
dc.type |
TCCgrad |
pt_BR |