dc.description.abstract |
A crescente complexidade estrutural e operacional do Sistema Interligado Nacional (SIN)
tem impulsionado a pesquisa e o desenvolvimento de aplicações baseadas em dados de
sincrofasores destinadas ao monitoramento, proteção e controle do sistema elétrico. Em
particular, a integração de sistemas HVDC-LCC (High Voltage Direct Current- Line
Commutated Converter) ao SIN apresenta alguns desafios, especialmente no que se refere
às falhas de comutação e seus impactos no desempenho dinâmico do sistema. Este trabalho
busca estudar a aplicação de indicadores de severidade, calculados a partir de dados de
sincrofasores para quantificar os efeitos sistêmicos de falhas de comutação em elos HVDC
LCC. Foram implementadas e testadas metodologias de análise baseadas em dados de
PMUs (Unidades de Medição Fasorial), com o objetivo de ampliar a observabilidade dos
efeitos decorrentes de eventos envolvendo múltiplas falhas de comutação no comportamento
dinâmico do SIN. Os resultados obtidos confirmam a viabilidade da abordagem proposta,
indicando que os indicadores de severidade propostos podem contribuir para a definição
de estratégias operacionais, bem como para a melhoria da representação das falhas de
comutação em simulações da dinâmica do sistema elétrico. |
pt_BR |
dc.description.abstract |
The increasing structural and operational complexity of the Brazilian Interconnected
Power System (BIPS) has driven the research and development of applications based on
synchrophasor data for monitoring, protection and control of the electrical system. In
particular, the integration of HVDC-LCC (High Voltage Direct Current- Line Commu
tated Converter) systems into the BIPS presents some challenges, especially regarding
commutation failures and their impacts on the dynamic performance of the power system.
This work aims to study the application of severity indicators calculated from synchropha
sor data to quantify the systemic effects of commutation failures in HVDC-LCC links.
Methodologies based on data from PMUs (Phasor Measurement Units) were implemented
and tested, with the aim of expanding the observability of the effects resulting from events
arising multiple commutation failures on the dynamic behavior of the BIPS. The results
obtained confirm the feasibility of the proposed approach, indicating that the proposed
severity indicators can contribute to the definition of operational strategies, as well as
to the improvement of the representation of commutation failures in simulations of the
dynamics of the electrical system. |
pt_BR |
dc.format.extent |
90 f. |
pt_BR |
dc.language.iso |
por |
pt_BR |
dc.publisher |
Florianópolis, SC. |
pt_BR |
dc.rights |
Open Access. |
en |
dc.subject |
Sincrofasores |
pt_BR |
dc.subject |
HVDC |
pt_BR |
dc.subject |
Indicadores |
pt_BR |
dc.subject |
Comutação |
pt_BR |
dc.title |
Aplicação de indicadores de severidade baseados em sincrofasores para quantificação dos efeitos de falhas de comutação no desempenho dinâmico do Sistema Interligado Nacional |
pt_BR |
dc.type |
TCCgrad |
pt_BR |
dc.contributor.advisor-co |
Silva, Daniel Sousa da |
|